The energy-efficient wall-mounted cooling unit Blue e+ Outdoor can be used worldwide, thanks to its multi-voltage capability, and is suitable for use with Toptec project solutions, for example.
Average 75% energy savings thanks to speed-regulated components and heat pipe technology
Longer service life of the components inside the enclosure and the cooling unit due to component-friendly cooling
Intuitive operation due to touch display and intelligent interfaces
Aluminium AlMg3
UV-resistant pure polyester
Condenser with hydrophobic RiNano coating
Integral electric condensate evaporation
Fully wired ready for connection (plug-in terminal strip)
Mounting frame for universal attachment to outdoor enclosures for external, partial internal and full internal mounting.
Assembly parts
For remote monitoring and networking of cooling units and chillers in the Blue e+ generation, please use the IoT interface (Model No. 3124.300). Increase machine availability and process reliability with remote monitoring of device data, statuses and system messages.
Cooling output L35 L35/50 Hz: 1.5 kW
Cooling output L35 L35/60 Hz: 1.5 kW
Cooling output L35 L50/50 Hz: 1.13 kW
Cooling output L35 L50/60 Hz: 1.13 kW
110 V - 240 V, 1~, 50 Hz/60 Hz
380 V - 480 V, 3~, 50 Hz/60 Hz
By downloading the software, a contract is concluded between the contractual partner and Rittal for the free use of the software in accordance with these licence conditions.
Tolerance: 110 V -10% (99 V) and 240 V +10% (264 V) / 380 V -10% (342 V) and 480 V +6% (509 V)
0.62 kW
Power consumption L35 L35/50 Hz: 0.57 kW
Power consumption L35 L35/60 Hz: 0.57 kW
Power consumption L35 L50/50 Hz: 0.64 kW
Power consumption L35 L50/60 Hz: 0.64 kW
e+ controller (factory setting +35 °C)
Width: 415 mm
Height: 990 mm
Depth: 280 mm
Width: 467 mm
Height: 1,042 mm
Depth: 280 mm
Universal installation (external mounting, partial internal mounting, full internal mounting)
with mounting frame: internal circuit IP56
without mounting frame: internal circuit IP 54
with mounting frame: UL Type 12/3R/4
without mounting frame: UL Type 12/3R
External circuit: 895 m3/h
Internal circuit: 700 m3/h
Refrigerant: R134a
Quantity: 0.75 kg
Global Warming Potential (GWP): 1,430
CO₂ equivalent (CO₂e): 1.07 t
Refrigeration factor L35 L35 (EER) 50 Hz: 2.61
Refrigeration factor L35 L35 (EER) 60 Hz: 2.61
Enclosure type: Toptec
Width: ≥ 600 mm
Height: ≥ 1,200 mm
9828.550
9868.550
9888.550
20 °C...50 °C
-30 °C...60 °C
3 °C...60 °C
-30 °C...45 °C
-40 °C...70 °C
2.4
67 dB(A)